Standards of Performanance of RVPN for the year 2004-05
|
S. No. |
Particulars |
Level specified by the Commission |
Level Achieved by RRVPNL during 2004-05 |
||||||
|
33 kV |
11 KV |
||||||||
|
1. |
System Availability |
Level –3 |
98% |
99.585 |
99.31 |
||||
|
2. |
Voltage Profile |
Class |
Max. |
Min. |
Max. |
Min. |
|||
|
400 kV |
420 |
360 |
434 |
370 |
|||||
|
220 kV |
245 |
200 |
250 |
159 |
|||||
|
132 kV |
145 |
120 |
149 |
90 |
|||||
|
66 kV |
72.6 |
59.4 |
-- |
-- |
|||||
|
33 kV |
34.98 |
30.03 |
39 |
23.6 |
|||||
|
11 kV |
11.66 |
10.01 |
12.9 |
8.3 |
|||||
|
3. |
Voltage Unbalance |
Level –3 |
|||||||
|
220 kV and above |
2% |
400 kV |
Nil |
||||||
|
220 kV |
9.5 |
||||||||
|
Below 220 kV |
3% |
132 kV |
9.8 |
||||||
|
33 kV |
10.51 |
||||||||
|
11 kV |
9.23 |
||||||||
|
4. |
Voltage Variation Index |
Level –3 |
For higher Voltage |
For lower Voltage |
|||||
|
400 kV |
1.125% |
400 kV |
2.215 |
0.71 |
|||||
|
220 kV |
1% |
220 kV |
2.369 |
2.709 |
|||||
|
132 kV |
1% |
132 kV |
1.889 |
3.08 |
|||||
|
66 kV |
1% |
66 kV |
-- |
-- |
|||||
|
33 kV |
2.856 |
2.796 |
|||||||
|
11 kV |
2.924 |
3.045 |
|||||||
|
5. |
Frequency Variation Index |
As per IEGC |
¨ |
||||||
|
6. |
Loss of Load Expectation (LOLE) |
Level –3 |
2% |
$ |
||
|
7. |
System Average Interruption Frequency Index (SAIFI) |
33 kV |
11 kV |
|||
|
Level –3 |
18 per year |
12.53 Nos. |
9.66 Nos. |
|||
|
8. |
System Average Interruption Duration Index (SAIDI) |
33 kV |
11 kV |
|||
|
Level –3 |
8 hrs. / year |
8.06 Hrs./ year |
6.52 Hrs./ year |
|||
|
9. |
Total Harmonic Distortion (THD) |
Level –3 |
¨ |
|||
|
IEC Std. 1000-4-7 or |
||||||
|
IEEE Std. 519 |
||||||
|
Not to Exceed 1% at EHV Interconnection point. |
||||||
|
10. |
Safety Manual |
To be published |
Draft under finalization |
|||
|
11. |
List of Sub-Station Where current Unbalance noticed. |
¨ |
||||
Note :- The authenticity of figures in respect of voltage profile, voltage un-
¨ The measurements of these parameters are not being done at any EHV GSS because the required instruments are not available for the measurement of these parameters.
$ The information is not available and can not be quantified at present.